Permit: T06CM03783

Parcel: 133170630


Addresses:

350 N WILMOT RD


Inspection Status: Approved

Inspection History: ENGINEERING - FINAL

Permit Number - T06CM03783

Inspection Description - ENGINEERING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/21/2007 ENGINEERING - FINAL Approved THE PREVIOUSLY NOTED COMMENTS HAVE BEEN CLEARED AT THIS TIME. THIS SITE HAS BEEN CLEARED FOR THE FINAL C OF O FROM THE ENGINEERING DEPARTMENT.
09/19/2007 ENGINEERING - FINAL Partial Approval 1. PROVIDE TRUNCATED DOMES WHERE SHOWN ON THE PLAN OR REVISE DRAWINGS.
2.PERMANENT C OF O NOT TO BE GIVEN UNTIL THE FINAL GRADING INSPECTION #09190 FOR T07BU00616 IS COMPLETED AND APPROVED
06/29/2007 ENGINEERING - FINAL Cancelled
06/28/2007 ENGINEERING - FINAL Partial Approval OK FOR TEMPORARY C OF O.
1. PERMANENT C OF O NOT TO BE GIVEN UNTIL THE FINAL GRADING INSPECTION #09190 FOR T07BU00616 IS COMPLETE AND APPROVED.
2. PROVIDE A C.O.T. APPROVED GRADING PLAN THAT ADDRESSES ALL REVISIONS:
A. DRAINAGE SWALE AT SOUTH AND WEST PERIMETERS OF SITE.
B. BUBBLE UP ROOF DRAINAGE AT NORTH SIDE OF SITE.
C. HANDICAP PARKING RE-LOCATIONS.

NOTE: THE ENGINEERS WERE INFORMED THAT REFERENCE TO THE PLUMBING PLAN REGARDING THE BUBBLE UP RAIN DRAINAGE SYSTEM WAS NOT ACCEPTABLE. A DETAIL OF THE BUBBLE UP/CATCH BASIN CONSTRUCTION MUST BE PROVIDED ON THE REVISED GRADING PLAN.
06/27/2007 ENGINEERING - FINAL Not ready for Inspection DISCUSSED REQUIREMENTS FOR A TCO
06/26/2007 ENGINEERING - FINAL Denied 1. PROVIDE A C.O.T. APPROVED COPIES OF THE GRADING AND SITE PLANS THAT SHOW ALL REVISIONS.
2. ALL HANDICAP PARKING SPACES MUST HAVE LESS THAN 2% SLOPE IN ALL DIRECTIONS, INCLUDING (3) SPACES SOUTH OF OUTPATIENT BUILDING (SEE PAGE X.1.1)
3. ADDRESS STANDING WATER AND BUBBLE-UP FOR EASTERN ROOF DRAINAGE (UPPER LEVEL). SHOW BUBBLE-UP STRUCTURE ON THE REVISED GRADING AND SITE PLANS.
4. PROVIDE POSITIVE DRAINAGE IN SWALE ON SOUTH AND WEST PERIMETERS.
5. PROVIDE A LETTER OF CERTIFICATION FROM THE ARIZONA REGISTERED P.E. THAT CERTIFIES THE SITE AND DRAINAGE CONSTRUCTION.

DOC 784-4918
06/12/2007 ENGINEERING - FINAL Denied 1. PROVIDE TRUNCATED DOMES WHERE PEDESTRIAN ACCESSWAYS CROSS STREETS AND DRIVEWAYS.
PER: ANSI 406.12, 406.13, AND 406.14
1. NORTHWEST CORNER OF SITE.
2. NORTH SIDE OF SITE AT THE CROSS WALK
3. EAST SIDE OF SITE AT THE CROSS WALK
2. PAINT STRIPED CROSS WALKS,
3. PROVIDE POSITIVE DRAINAGE IN SWALE ON SOUTH AND WEST PERIMETERS.
4. PROVIDE A LETTER OF CERTIFICATION FROM THE ARIZONA REGISTERED P.E. THAT CERTIFIES SITE AND DRAINAGE CONSTRUCTION.

DOC 784-4918
05/11/2007 ENGINEERING - FINAL Denied NOT READY - CONSULTATION INSPECTION
1. PROVIDE TRUNCATED DOMES AT RAMP TO HANDICAP PARKING SPACES AT NORTHEAST CORNER OF SITE AT KEYNOTE #60 PAGE C-2
2. (3) 5' CURB OPENINGS ARE OK, CONSTRUCT THE RAMPS TO PC/COT DETAIL 207.