Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CONSTRUCTION POWER
Permit Number - T06CM03783
Inspection Description - ELECTRIC - CONSTRUCTION POWER
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/10/2007 | ELECTRIC - CONSTRUCTION POWER | Approved | IVRS - Inspection :* | |
06/13/2007 | ELECTRIC - CONSTRUCTION POWER | Not ready for Inspection | IVRS - Inspection :* 1) GROUNDING ELECTRODE CONDUCTOR TO BE PER 250.64 (E) 2) ONLY ONE CONDUCTOR TO A LUG 3) PLEASE MOVE GEC TO ACCESSIBLE DISCONNECT 4) INSTALL REJECTION PINS AND FUSES 5) FILL UNUSED OPENINGS IN PANEL 6) LABEL EQUIPMENT 7) PLEASE ADD 02062 AND POST BOND FOR TEMP POWER FOR TEST |