Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM03783
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/10/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
07/02/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
06/22/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. RECEPTACLE COVER TO BE AS PER 406.8 - WEATHERPROOF WHETHER OR NOT PLUGGED INTO 2. FILL UNUSED OPENINGS IN CONDUITS & BOXES 3. PLEASE PROVIDE A LETTER VERIFYING POLE HEAD MAKEUP 4. IDENTIFY CABLE CONDUCTOR TO UNGROUNDED CONDUCTORS. OK STAIRWELL LIGHTING 2ND LEVEL OK 2ND LEVEL PENDANT LIGHTS 5. LIGHTING SCHEDULE CALL FOR "WET LOCATION" EM & EXIT LIGHTING. |
|
05/01/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK 2ND FLOOR DOWN SOUTH |
|
04/30/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK 2ND FLOOR NORTH & UPPER RAMP OK TO COVER |
|
04/30/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
04/25/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
04/24/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK 3RD FLOOR SOUTH 1/2 OK RAMP DOWN & CENTER TO 2ND FLOOR |
|
04/19/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. FILL UNUSED OPENING WITH LISTED PARTS 2. PROTECT PVC JACKET FROM SHARP METAL EDGES OK 3RD FLOOR NORTH 1/2 |