Inspection History Details
Inspection Status: Approved
Inspection History: REINFORCED MASONRY PRE-GROUT
Permit Number - T06CM03783
Inspection Description - REINFORCED MASONRY PRE-GROUT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/02/2007 | REINFORCED MASONRY PRE-GROUT | Approved | IVRS - Inspection :* | |
05/22/2007 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* MECHANICAL ROOM NORTH & SOUTH WALLS TO 10.7" A.F.F.E WEST WALL 9.3" A.F.F.E IN COMPLIANCE WITH APPROVED PLANS AND SPECIFIC DETAILS. RFI TO TOPOUT BY DONALD E 5/7/07 |
|
05/21/2007 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* ELEVATOR TOWER @ TOPOUT IN COMPLIANCE WITH SPECIFIC DETAIL 10 ON SHEET S10.3 ELECTRICAL ROOM OK TO TOPOUT MECHANICAL ROOM 12.5 CMU COURSES A.F.F.E |
|
05/18/2007 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* ELEVATOR SHAFT PERIMETER 29.7" - 33.7" A.F.F.E OF SHAFT WEST NORTH ELECTRICAL ROOM WALL @ TOP OUT IN ACCORDANCE WITH APPROVED PLANS AND RFI ON 5/7/07 BY LEO WHITELEY P.E. |
|
05/16/2007 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* THIS INSPECTION COVERS THE FOLLOWING AREA EAST STAIR/MECH ROOM IN COMPLIANCE WITH LAYOUT ON SHEET S10.2 SPECIFIC DETAIL 9/S4.1, S4.3/3, MECH. ROOM 32" A.F.F.E; ELEVATOR 25.7"-29.7" A.F.F.E |
|
05/15/2007 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* DOC OF BFL SUNDT WOULD LIKE FOR YOU TO CALL HIM 1/2 HR BEFORE ----- 784-4918 THIS INSPECTION COVERS REINFORCING ON CMU WALL FOR EAST ELEVATOR, LAYOUT ON SHEET S10.2 AND SPECIFIC DETAILS 6/SG.1, S1.0, S4.3/3, 21.7" - 25.7" A.F.F OF INTERIOR SLAB OF ELEVATOR. |
|
05/14/2007 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* | |
05/11/2007 | REINFORCED MASONRY PRE-GROUT | Not ready for Inspection | IVRS - Inspection :* | |
05/10/2007 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* | |
05/08/2007 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* REINFORCING PLACEMENT AT THE FOLLOWING LOCATIONS 4.5/D-C.5, C.5/4.5-4.7 48" A.F.F.E FIRST LIFT ELECTRIC ROOM ELEVATOR C.3/11 ALL WALLS 6' A.T.O.F OK TO GROUT |
|
05/03/2007 | REINFORCED MASONRY PRE-GROUT | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE SPECIAL INSPECTION REPORT IN COMPLIANCE WITH U.A.C & CH17 INCOMPLETE WORK |