Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING PRE-SLAB
Permit Number - T06CM03783
Inspection Description - BUILDING PRE-SLAB
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/02/2007 | BUILDING PRE-SLAB | Approved | IVRS - Inspection :* | |
05/14/2007 | BUILDING PRE-SLAB | Partial Approval | IVRS - Inspection :* 1. THIS INSPECTION COVERS THE FOLLOWING AREA EAST STAIR MECH. ROOM LAYOUT ON SHEET S10.2/2 SPECIFIC DETAIL ON SHEET S4.1/9 IN ACCORDANCE WITH APPROVED PLANS. PROVIDE RFI FOR 2 #5 DOWELS MISSED 8" O.C IN ACCORDANCE WITH DETAIL 1 ON SHEET S4.2 2. THIS INSPECTION COVERS THE FOLLOWING AREA, EAST ELEVATOR CMU REINFORCING AT 8'-12' A.F.F.E AND 17'-21' A.F.F.E -- OK TO GROUT. |
|
05/11/2007 | BUILDING PRE-SLAB | Partial Approval | IVRS - Inspection :* 1) NOTE: THIS INSPECTION COVER THE FOLLOWING AREA EAST STAIR (MECH ROOM) IN COMPLIANCE WITH LAYOUT ON SHEET S10.2 AND SPECIFIC DETAIL ON SHEET S4.1/3 |
|
05/10/2007 | BUILDING PRE-SLAB | Partial Approval | IVRS - Inspection :* 1. NORTHWEST STAIR FOOTINGS AND SLAB IN COMPLIANCE WITH DETAIL 2 ON SHEET S10.3 AND DETAIL 1 ON SAME PAGE OR SHEET. 2. REINFORCED MASONRY PRE-GROUT INSPECTION COVER 12' A.F.F. OF OK TO GROUT COMPLETE ELECTRICAL ROOM AND CALL FOR INSPECTION PRIOR TO GROUT. |
|
05/09/2007 | BUILDING PRE-SLAB | Cancelled | ||
05/01/2007 | BUILDING PRE-SLAB | Partial Approval | IVRS - Inspection :* THIS INSPECTION COVERS LEVEL 2 ON THE FOLLOWING AREAS B.5-CO/1.0-11.0, D.0-D.5/1.0-11.0 IN COMPLIANCE WITH APPROVED PLANS AND SPECIFIC DETAILS SPECIAL INSPECTION REPORT PROVIDED |
|
04/30/2007 | BUILDING PRE-SLAB | Partial Approval | IVRS - Inspection :* LEVEL 2 GRIDLINES A.0-B.3/1.0-11.0 C.0-C.5/1.0-4.5 IN COMPLIANCE WITH APPROVED PLANS AND SPEC. PLUS ELECTRICAL ROOM FOUNDATION IN COMPLIANCE WITH DETAIL 7 ON SHEET S4.1 SPECIAL INSP. REPORT PROVIDED |
|
04/27/2007 | BUILDING PRE-SLAB | Partial Approval | IVRS - Inspection :* 3RD FLOOR SLAB, SPECIFIC DETAIL ON SHEET S2.3 GRIDLINE D-E/1-11, E-F/2-10 3RD FLOOR SLAB C-D/8.5-11 LEVEL 2 TO 3 C.5/D.0/1.0-9 + C.5-D.0/9-11 OK RAMP 2 TO 3 C-D/1-11 SPECIFIC DETAIL FOR ALL ABOVE IN COMPLIANCE WITH LAYOUT AND SPEC. ON SHEET S2.3 |
|
04/26/2007 | BUILDING PRE-SLAB | Partial Approval | IVRS - Inspection :* THIS INSPECTION COVERS 3RD FLOOR LEVEL REINFORCING ON SLAB. GRIDLINES B.5-C.0/1.0-11 D-D.5/10-11 IN ACCORDANCE WITH APPROVED PLANS AND SPECIFIC DETAILS. |
|
04/25/2007 | BUILDING PRE-SLAB | Partial Approval | IVRS - Inspection :* 1. 3RD LEVEL A-B.5 AND C-C.5 2. RAMP 2-3 C-C.5 OK |
|
04/24/2007 | BUILDING PRE-SLAB | Partial Approval | IVRS - Inspection :* 1. FINISH BULK HEAD 2. FINISH CHAIRING STEEL 3. INSTALL CORD STEEL AT CORNERS PER KEYNOTE B FOR SLAB REINFORCEMENT PP S2.2 4. CORD STEEL PER KEYNOTE A - PP S2.2 AND 2 #4 PER DETAIL 5. PLEASE HAVE ALL STEEL WORK READY AT LEAST ONE DAY AHEAD OF YOUR POUR SCHEDULE |
|
04/23/2007 | BUILDING PRE-SLAB | Partial Approval | IVRS - Inspection :* PROGRESS MEETING FOR PARKING FLOOR TOPPER POUR AT ALL FLOORS TO BEGIN THUR. 4/26/07 @ 2 AM RECALL FOR TOMORROW & WED |