Permit: T06CM03771
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/07/2007 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* OK FOR SHEETROCK |
|
| 02/21/2007 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio CORRECTIONS STILL HAVE NOT BEEN MADE PAY A REINSPECTION FEE PRIOR TO NEXT INSPECTION |
|
| 02/13/2007 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* NO CORRECTIONS HAVE BEEN MADE |
|
| 02/07/2007 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ELECTRIC WIRES CONTACTING WATER HEATER VENT 2) PROVIDE MINIMUM 1" CLEARANCE 3) REMOVE 2 X 4 BLOCK UNDER VENT PIPE 4) VENT DOES NOT HAVE ENOUGH SLOPE 5) RAISE FIRE BLOCK AT TOP OF VENT AND SLOPE VENT MORE 6) OK TO INSULATE BLDG |