Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/25/2006 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 07/24/2006 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. FIXTURES TO BE SUPPORTED ON OPPOSITE CORNERS WITH SUPPORT WIRES. 2. SUPPORT FIXTURE WHIPS OFF THE GRID 3. FINISH ELECTRICAL DEMOLITION 4. REMOVE OR TAG ALL UNUSED LOW VOLTAGE WIRING 5. FINISH LOW VOLTAGE WIRING AND MAKE SURE IT IS SUPPORTED FROM STRUCTURE AND NOT CEILING GRID OR ELECTRICAL EQUIPMENT, ALSO RAN IN A NEAT AND WORKMAN LIKE MANNER 6. HAVE SOME OVERFILLED AND UNGROUNDED J-BOXES CORRECT AS NEEDED. |