Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/07/2006 | FRAMING | Approved | IVRS - Inspection :* | |
| 12/04/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEAL VAPOR BARRIER |
|
| 11/30/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEAL STUCCO VAPOR BARRIER IN BATHROOM 2) MAXIMUM ALLOWED NUMBER OF FIXTURE UNITS ON 1/2" PEX AT 46 PSI IS 7 UNITS PRESENTLY 8 FIXTURE UNITS INSTALLE-HOSE BIB, SHOWER AND W/C ON 1/2 PEX |
|
| 11/24/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE A 10 FOOT HEAD OF WATER ON DRAIN WATER VENT PLUMBING 2) PEX PLUMBING MUST BE 12" FROM RECESSED LIGHTS 3) STUCCO VAPOR BARRIER IS CUT MUST BE SEALED 4) BEDROOM MUST HAVE 110 VOLT HARD WIRES SMOKE DETECTOR TIED IN TO EXISTING SMOKE DETECTOR SYSTEM 5) TWO MANY FIXTURES ON 1/2" PEX ONLY TWO FIXTURES ALLOWED |