Permit: T06CM03753

Parcel: 140441290


Addresses:

8026 S FARMBELT DR

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
12/07/2006 FRAMING Approved IVRS - Inspection :*
12/04/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEAL VAPOR BARRIER
11/30/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEAL STUCCO VAPOR BARRIER IN BATHROOM
2) MAXIMUM ALLOWED NUMBER OF FIXTURE UNITS ON 1/2" PEX AT 46 PSI IS 7 UNITS PRESENTLY 8 FIXTURE UNITS INSTALLE-HOSE BIB, SHOWER AND W/C ON 1/2 PEX
11/24/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE A 10 FOOT HEAD OF WATER ON DRAIN WATER VENT PLUMBING
2) PEX PLUMBING MUST BE 12" FROM RECESSED LIGHTS
3) STUCCO VAPOR BARRIER IS CUT MUST BE SEALED
4) BEDROOM MUST HAVE 110 VOLT HARD WIRES SMOKE DETECTOR TIED IN TO EXISTING SMOKE DETECTOR SYSTEM
5) TWO MANY FIXTURES ON 1/2" PEX ONLY TWO FIXTURES ALLOWED