Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/03/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 07/02/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 06/27/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSTALL CORRECT BACKFLOW PREVENTION DEVICE AT POOL FILL - PROTECT EXPOSED PLASTIC |
|
| 06/20/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* - PROVIDE TEMPERATURE LIMITING DEVICES FOR PUBLIC LAVATORIES. - PRESSURE VACUUM BREAKER OR RPA ASSEMBLY REQUIRED AT BAPTISMAL FILL. PROVIDE CERTIFICATION. - HB VAC BREAKERS - ROOF DRAIN TERMINATIONS |
|
| 06/13/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CLOSET FLANGES OK 2) FOR FINAL: BACKFLOW PREVENTION ASSEMBLY REQUIRED FOR POOL/BAPTISMAL FILL 3) INSULATE EXPOSED DOMESTIC WATER PIPING 4) INSTALL HB VAC BREAKERS 5) PROVIDE REVISED PLANS 6) INSTALL ALL FIXTURES 7) ADJUST PRESSURE IN EXP TANK TO MATCH WATER PRESSURE |
|
| 05/24/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* |