Permit: T06CM03748

Parcel: 13312004H

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/02/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
OK FINAL
07/03/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. FINISH #1 OUTSIDE PREVIOUS INSPECTION
2. INSTALL WALL LIGHT

OK TCO SUBJECT TO DETERMINATION OF S.LONG
07/02/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. NEED MANUFACTURES INSTUCTIONS FOR MOTION SENSOR
2. CIRCUIT DIRECTORIES TO BE PERMANENT
3. HAVE ELECTRICIAN OPEN MAIN SWITCH GEAR & PANEL "H"

ROOF
1. IDENTIFY GROUND IN DISCONNECT
2. RECEPTACLE COVER TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO -- 406.8

OUTSIDE
1. PLEASE VERIFY LISTING FOR HYDRO EQUIPMENT
06/28/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
MEET ELECTRICIAN -- SEE LIST
1. CLEAN AND REDO PANEL FEEDER TERMINATIONS
2. SHEETMETAL SCREWS NOT ALLOWED FOR GROUNDING
3. CLEAN EXCESS MATERIAL FROM FLOOR BOXES
06/27/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 314.20
2. PANEL DIRECTORIES TO BE AS PER 408.4 --
NO ABBREVIATIONS
3. PLEASE HAVE ELECTRICIAN PRESENT TO OPEN EQUIPMENT
4. PROVIDE MANUFACTURES INSTRUCTIONS FOR MOTION SWITCH
06/20/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELLED