Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/02/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK FINAL |
|
| 07/03/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. FINISH #1 OUTSIDE PREVIOUS INSPECTION 2. INSTALL WALL LIGHT OK TCO SUBJECT TO DETERMINATION OF S.LONG |
|
| 07/02/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. NEED MANUFACTURES INSTUCTIONS FOR MOTION SENSOR 2. CIRCUIT DIRECTORIES TO BE PERMANENT 3. HAVE ELECTRICIAN OPEN MAIN SWITCH GEAR & PANEL "H" ROOF 1. IDENTIFY GROUND IN DISCONNECT 2. RECEPTACLE COVER TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO -- 406.8 OUTSIDE 1. PLEASE VERIFY LISTING FOR HYDRO EQUIPMENT |
|
| 06/28/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* MEET ELECTRICIAN -- SEE LIST 1. CLEAN AND REDO PANEL FEEDER TERMINATIONS 2. SHEETMETAL SCREWS NOT ALLOWED FOR GROUNDING 3. CLEAN EXCESS MATERIAL FROM FLOOR BOXES |
|
| 06/27/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 314.20 2. PANEL DIRECTORIES TO BE AS PER 408.4 -- NO ABBREVIATIONS 3. PLEASE HAVE ELECTRICIAN PRESENT TO OPEN EQUIPMENT 4. PROVIDE MANUFACTURES INSTRUCTIONS FOR MOTION SWITCH |
|
| 06/20/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELLED |