Permit: T06CM03748

Parcel: 13312004H

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
07/02/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
06/28/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
06/27/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
06/20/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELLED
06/01/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK VDV CABLING IN CLOUDS
05/29/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK CANS EAST CLOUD
1. SUPPORT VDV CABLING 725.6
2. HAVE BUILDING INSPECTOR VERIFY HOLES IN BEAMS
ROOM 103
3. FINISH FURRING WALL TO SEE CABLE PROTECTION
ROOM 103
05/25/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK BATHROOMS
1. SUPPORT ALL VDV CABLING AS PER 725.6
05/24/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
NO WORK PROGRESS
05/23/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. ACCESS TO BE CLEAR OF CABLES
2. PROTECT CABLES ACROSS JOINTS & MIDSPANS
3. WHAT ARE EXCESS LOOPS OF M/C CABLES IN BATHROOMS

OK BACK SOFFIT CANS
NOTES FOR JUNCTION BOXES
ACCESS APPLY
OK CHAPEL CANS
OK BATHROOM WALLS ONLY

* VERIFY LISTING FOR STAGE LIGHTING
05/18/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WEST CLOUD
1. MOVE M/C IN CHANNEL OF STUDS TO PROTECT
2. REMOVE TEMP LIGHTING
05/17/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK CANS OUTSIDE CORNER SOFFITS & CENTER SOFFIT
05/03/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
04/26/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK PVC CONDUIT IN SLAB/UNDER SLAB IN NAVE
04/19/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK PVC CONDUIT AV ROOM
OK CEILING AV ROOM
1. SEAL UNUSED OPENINGS JUNCTION BOX
04/17/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. TIGHTEN LOOSE FITTING AND SUPPORT 3RD EXTENDER BOX
OK WALLS BATHROOMS AND FATHERS OFFICE

* DOES ARTICLE 68D APPLY TO POOL
04/13/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
NO ONE PRESENT TO VERIFY WHAT TO INSPECT
04/11/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELLED
04/02/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALL 104-106 SUBJECT TO LETTERS FROM ENGINEER

1. SUPPORT M/C CABLE WITHIN 12"
2. PROTECT M/C CABLE IN CHANNEL OR MOVE OUT
3. CONDUIT TO BE 3/4" PER PLANS OR PROVIDE A LETTER AUTHORIZING USAGE.
4. PLEASE PROVIDE A LETTER AUTHORIZING USE OF M/C CABLE.
03/26/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) OK FACE WALL SOFFIT
2) JUNCTION BOXES TO BE ACCESSIBLE
03/13/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER CEILING NAVE
HARD LID