Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING PRE-SLAB
Permit Number - T06CM03738
Inspection Description - BUILDING PRE-SLAB
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/16/2007 | BUILDING PRE-SLAB | Approved | ||
01/03/2007 | BUILDING PRE-SLAB | Partial Approval | IVRS - Inspection :* B-C GRID 3-A SLAB OK 02005 -- ELEC. GROUND FOR LIGHT POLES OK (20' #4 CU AND CLAMPED TO REBAR) + 2 EACH 3/4" PVC CONDUIT |
|
12/27/2006 | BUILDING PRE-SLAB | Partial Approval | IVRS - Inspection :* GRIDLINE B/9-3, B 1/2 9-3 DETAIL ON RAMP 3/S4.1 |
|
12/20/2006 | BUILDING PRE-SLAB | Partial Approval | IVRS - Inspection :* B-C/9-11 PRESLAB AND RFI PROVIDED |
|
12/19/2006 | BUILDING PRE-SLAB | Partial Approval | IVRS - Inspection :* 1. TOPPING SLAB ON DECK OK PER REVIEW OF SPECIAL INSP. REPORTS (LEERAY) 2. MUST PROVIDE RFI FOR WWF THROUGH CENTRAL JOINT FOR SLAB ON GRADE AND DELETION OF 1 #4 IN CURB AT TOE DOWN (LEE RAY) 3. B-C/9-11 OK TO PLACE, PROVIDE RFI NOTED IN #2 ABOVE (LEERAY) |
|
12/13/2006 | BUILDING PRE-SLAB | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE 2" X 2" KEY WAY CONTROLS WHEN YOU CONCRETE SLAB FINISH OR BY SECTIONS POUR. 2. PROVIDE SLAB ON GRADE TORN DOWN WITH #4 NOSING BAR AND (2) #4 CONT. 3. PROVIDE THE CORRECT SEPARATION BETWEEN WWF (WIRE WELD FAB) MESH ACCORDING WITH APPROVED OR PLAN T/3 DETAIL ON SHEET S4.1/5 4. NO SUPERINTENDENT ON JOB SITE. |