Permit: T06CM03721

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
10/12/2006 FRAMING Approved IVRS - Inspection :*
10/11/2006 FRAMING Partial Approval IVRS - Inspection :*
10/10/2006 FRAMING Partial Approval IVRS - Inspection :*
1) COMPLETE PRIOR ITEMS NOT DONE 1, 5, 7, 9 & 10
10/06/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEE DETAIL AD513 FOR STAIR INSTALLATION DETAIL
2) STUCCO MESH STILL BEING INSTALLED
3) ROMEX OUT OF CEILING DINING
4) REMOUNT BOXES BEDROOM 3
5) NEED 12" CLEARANCE PEX TO CAN LIGHT AT TUB KITCHEN CEILING
6) KITCHEN CEILING AT TUB
7) SUPPORT ABS WITH BLOCKS EVERY 4'
8) FIRE STOP LINE SET AT BLOCKING IN GARAGE
9) NEED EXHAUST FAN MASTER BATH-WIRE IN
10) 2ND A/C CONDENSATE DRAIN TO BE IN OBVIOUS LOCATION
08/30/2006 FRAMING Not ready for Inspection IVRS - Inspection :*
1) ADD #5 SHEAR WALL AT STAIRS
2) ADD 2-2 X 10 BEAM AT GREAT ROOM
3) OK TO WRAP
08/28/2006 FRAMING Not ready for Inspection IVRS - Inspection :*