Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T06CM03714
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/20/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
11/14/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. CLOSET FLANGES OK 2. GRAY WATER TANK & DISTRIBUTION PIPING OUTSIDE TANKS UNDERGROUND NO TEST PER PLAN |
|
11/05/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. RPPBP FOR RECLAIMED WATER OK RPPBP FOR DOMESTIC SUPPLY OK 2. 2ND FLOOR SHOWER HOLDING WATER |
|
09/12/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* HW PIPE INSULATION AT 2ND LEVEL TR OK AT EXTERIOR YARD WATER REPAIR - PROPER ALIGNMENT OF PVC FITTINGS IS REQUIRED AND THREAD CONNECTIONS DO NOT GET GLUE. |
|
09/10/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* TR#208 DWV W/TEST WATER PIPING IN TR AND OVERHEAD ABV TR OK INSTALL INSULATION NEED TO SEE SHOWER PAN LINER AND CLOSET FLANGE |
|
08/31/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* THE UPPERMOST TEN FEET OF THE NEXT PRECEDING SECTION SHALL BE TESTED ON A SECTIONAL TEST SO THAT NO JOINT OR PIPE SHALL BE INSTALLED WITHOUT AT LEAST TEN FEET OF HEAD PRESSURE. |
|
08/30/2007 | PLUMBING - INTERMEDIATE | Partial Approval | 1" RECLAIMED WATER FROM JANITOR SINK WALL TO STOOLS IN RESTROOM ONLY. OVERHEAD HOT & COLD AND IN WALL WATER FOR RESTROOM AREA OK 1. RECLAIMED SYSTEM TO BE PROPERLY IDENTIFIED BEFORE COVERING. 2. INSULATION TO BE INSTALLED PRIOR TO COVERING (2) 3" AREA DRAINS FROM 2ND LEVEL TO EXTERIOR WATER TEST OK |
|
08/22/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - 1ST LEVEL EAST BUILDING WASTE & VENT WATER TEST TO 2ND LEVEL OK - WATER PIPING INSULATION 1ST LEVEL EAST BLD. OK |
|
08/17/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* WATER TEST WASTE & VENT EAST BUILDING ONLY UP TO 2ND FLOOR LEVEL EXCEPT, WASHING MACHINE BOX IN MAMMAL ROOM AND AREA DRAINS ON 2ND COVER TO BE PER PLAN. WATER PIPING 1ST LEVEL AIR TEST FROM EXTERIOR STUB OUT FOR BUILDING EAST HALF ONLY OK |
|
08/15/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCELLED |
|
06/28/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* (4) 2" VENTS TEST TO 6' ABOVE 2ND LEVEL DECK AT SOUTHEAST CORNER WATER TEST OK |
|
06/04/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* AT ANIMAL HOLDING -- (4) 2" VENTS TO 16'4" OK 2" VENT IN ICE BLOCK AT BREAKROOM SINK TO 16'4" OK |
|
05/25/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* PER SENIOR BLD INSPECTOR ICE BLOCK SHALL NOT HAVE VERTICAL PIPING IN ANGULAR SPACE. |