Permit: T06CM03714


Addresses:

1100 S RANDOLPH WY


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T06CM03714

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
12/20/2007 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
05/31/2007 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
PROVIDE TEST ON PIPING
05/15/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
3" VENT FOR GRAY WATER AT NORTHWEST STUBBED UP AND OUT OF BUILDING 2' OK
05/04/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
FROM MANHOLE #3 TO EXISTING MACAQUE HOUSE CONNECTION, TO CONNECTION POINT #29 STUB UP WATER TEST OK. SHALL PROVIDE METAL FOR #29 TERMINATION FROM PAGE C3.0
05/03/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
WATER TEST 2" EXPANSION OF GRAY WATER DRAIN FOR FUTURE DRINK FOUNTAIN PER REDLINE ON SITE. P-11 TO BE SEEN AS INTERMEDIATE.
05/01/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
MANHOLE #1 VACUUM TEST OK
MANHOLE #2 VACUUM TEST OK
MANHOLE #3 VACUUM TEST OK

1. SHALL PROVIDE APPROVED DRAINAGE FITTINGS FOR BACK TO BACK P-11'S
04/27/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :
THROUGH BUILDING -- WATER TEST UNDERGROUND SANITARY SYSTEM OK EXCEPT P-11 TO BE TESTED AT LATER DATE.
WATER TEST UNDERGROUND GRAY WATER SYSTEM THRU BUILDING TO 2' EXTERIOR OK SHALL SEE GRAY WATER TANKS AND VENT AT LATER DATE.
04/25/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
FROM EXISTING MANHOLE TO NEW MANHOLE #1 AIR TEST OK
FROM MANHOLE #1 TO MANHOLE #2 AIR TEST OK
FROM MANHOLE #2 TO MANHOLE #3 AIR TEST OK
04/19/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
FROM MANHOLE #3 4" THRU 2-WAY CLEANOUT INTO BUILDING UNDERGROUND
APP 5' WATER TEST OK
04/13/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
MANHOLES STACKED OK
1. SHALL PROVIDE PRIVATE MANHOLE COVER LID ON EXISTING PRIVATE MANHOLE TIED INTO ON DOWNSTREAM END.
04/12/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
MANHOLE #2 & #3 BASES POURED
04/09/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) 8" SDR 35 CONTINUES TO MANHOLE #2 AND TO MANHOLE #3
2) 4" SDR 35 STUDS (2) APP 5' OUT OF MANHOLE #3 PER PLAN
3) BEDDING, LAYING, TRACER AND SHADING OK
04/06/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) 8" SDR 35 CONTINUES TO MAN HOLE #2, BEDDING, LAYING TRACER, SHADING AND BACKFILLING OK
04/05/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
8" SDR 35 SEWER CONTINUES WEST APP. 150' WEST OF MH#1 TOWARD MH#2 BEDDING, LAYING, TRACER, SHADING BACKFILLING & MARKER TAPE OK
04/04/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
MANHOLE BASE POURED FOR NEW MANHOLE #1
8" SDR APP 90' WEST TOWARD NEW MANHOLE #2
BEDDING, LAYING, SHADING OK
REVISED APPROVED PLAN ON SITE
EXISTING MANHOLE NOTE #9 IS PRIVATE
04/02/2007 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
SITE SEWER PRE CONST. MEETING WITH DEAN KG & SONS
GARY ADOLFSON PETERSON
REVISED PLAN DATED 2/26/07 RUDOLF ANDREW SERVING AS PER REDLINE DUE TO SITE CONDITION.
THIS PLAN SHALL BE APPROVED. INSTALLATION TO MEET NOTES ON THIS PLAN WITH TRACER WIRE PER
HOUSE BILL 2256
8" SDR PIPING INSTALLED FROM EXISTING (PUBLIC OR PRIVATE MANHOLE?) CONTACTED KEVIN VARNER TO VERIFY THIS AT FUTURE DATE. TO NEW MANHOLE #1 CONTINUES APP
40' UPSTREAM
BEDDING, LAYING OK
ALL PIPING TO HAVE TEST AT LATER DATE
VACUUM TESTING REQUIRED ON MANHOLES
VERIFICATION OF GRADE BY ENGINEER OR SURVEYOR FOR PIPING SHALL BE REQUIRED.