Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM03714
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/31/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
12/28/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* FINISH PREVIOUS ITEM |
|
12/27/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) SHEET METAL THREAD SCREWS NOT ALLOWED 250.8 2) CLEAN SURFACE UNDER LUGS 250.12 3) SUPPORT CONDUIT AND TIGHTEN FITTING 4) VERIFY LISTING OF BEAM CLAMP FOR BONDING 5) FINISH PREVIOUS ITEMS CIRCLED |
|
12/21/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ARRANGE CONDENSOR DISCONNECTS ON ROOF TO COMPLY WITH 110-26 FOR WORKING CLEARANCE. ALSO BRACE GFI RECEPT BOX 2) BOND BLDG STEAL 3) SELF TAPING SHEET METAL SCREWS NOT APPROVED FOR GROUNDING EQUIP LUGS, PER 250 NEC 4) SUPPORT CONDUIT PER NEC ROOM 204 5) INSTALL CT'S IN PANELS PER MANUFACTURER SPECS FOR MOUNTING OR USE APPROVED SUPPORTS. TIE CABELING IN A NEAT AND WORKMANSHIP LIKE MANNER CHECK PANEL LISTING FOR COMPATABILITY FOR CTS IN PANEL ROOM 204 6) BUBBLE COVERS REQUIRED FOR GFI RECEPTS OUTSIDE 7) SEE NOTS LAST INSPECTION FOR BUSHINGS REQUIRED ON CONDUIT TERMINATIONS #4 AND LARGER ROOM 208 ELECTRICAL PANEL |
|
12/20/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OVERCURRENT PROTECTION REQUIRED FOR SECONDARY'S FEEDING PANEL L2 WITHIN 25' OF TRANSFORMER. PER 240 NEC 2. REMOVE ALL PANEL, GUTTER, J-BOX COVERS FOR INSP. |