Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/09/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 03/14/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. LABEL DISCONNECT & BREAKER PER 690.14 NEC 2. INSTALL GROUNDING ELECTRODE CONDUCTOR PER 690.47 NEC (CONTINUOUS) 3. GROUND EQUIPMENT PER 690.43 NEC & 690.45 NEC 4. GROUNDING OF PANELS ON ROOF NEEDS TO BE CONTINUOUS SO REMOVAL OF PANEL WILL NOT INTERRUP CONTINUITY. 5. REMOVE PAINT FROM GROUND CONNECTORS AT JUNCTION BOXES. 6. INSTALL EMT PER NEC 358 7. INSTALL JUNCTION BOXES PER NEC 314.23 |