Permit: T06CM03698

Parcel: 116112200

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
04/09/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
03/14/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. LABEL DISCONNECT & BREAKER PER 690.14 NEC
2. INSTALL GROUNDING ELECTRODE CONDUCTOR
PER 690.47 NEC (CONTINUOUS)
3. GROUND EQUIPMENT PER 690.43 NEC & 690.45 NEC
4. GROUNDING OF PANELS ON ROOF NEEDS TO BE CONTINUOUS SO REMOVAL OF PANEL WILL NOT INTERRUP CONTINUITY.
5. REMOVE PAINT FROM GROUND CONNECTORS AT JUNCTION BOXES.
6. INSTALL EMT PER NEC 358
7. INSTALL JUNCTION BOXES PER NEC 314.23