Inspection History Details
Inspection Status: Denied
Inspection History: OUTDOOR LIGHTING FINAL
Permit Number - T06CM03672
Inspection Description - OUTDOOR LIGHTING FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/26/2007 | OUTDOOR LIGHTING FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* OUTSIDE LIGHTING DOES NOT MEET OUTSIDE LIGHTING CODE THIS IS A 0.108 ACRE LOT WITH 5960 ALLOWABLE LUMENS WHICH MAY HAVE 1296 UNSHIELDED; YOU HAVE 5100 UNSHIELDED. THE FIXTURE THAT YOU ARE USING DOES NOT MEET THE SPECS FOR FULL CUT OFF PER LIGHTING CODE PARAGRAPH 4.7 IF YOU FEEL THEY DO THEN PROVIDE DOCUMENTATION PER PARAGRAPH 4.7 |