Permit: T06CM03671

Parcel: 141094470


Addresses:

6346 E BOLDIN DR


Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T06CM03671

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/19/2007 BUILDING - FINAL Approved IVRS - Inspection :*
01/16/2007 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FIREPLACE HEARTH MUST BE 8" WIDER THAN OPENING ON EACH SIDE AND 16" IN FRONT AND BE OF NON COMBUSTIBLE MATERIAL
2) MARK FAN HEAT STRIP/FUSE LABEL FOR CORRECT SIZE
3) PROVIDE UNOBSTRUCTED ACCESS TO FAN/FURNACE
4) KITCHEN GFCI CIRCUITS NOT WIRED CORRECTLY
5) OUTDOOR LIGHTING FIXTURES DO NOT MEET OUTDOOR LIGHTING CODE. THEY HAVE VISIBLE LIGHT 90 DEGREE FROM GROUND AND FIXED LUMINOUS