Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T06CM03670
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/18/2007 | PLUMBING - ROUGH, SOIL | Approved | ||
07/17/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1) REVISE EXISTING PLAN TO CHANGE MAIN DRAIN TO 3" 2) PROVIDE A PLAN FOR EACH MODEL FOR DUEL TRUNK DRAIN SYSTEM WITH FIRST AND SECOND FLOOR DRAINS ON SEPERATE SYSTEMS WHEN BACK WATER VALVES ARE NEEDED |
|
07/14/2006 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ROUGH PLUMBING IS NOT LAYED OUT PER PLAN 2) ROUGH PLUMBING IS NOT SIZED PER PLAN 3) PLAN CALLS FOR 4" DRAIN 4) BUILD TO PLAN OR HAVE PLAN REVISED TO AS BUILT |