Permit: T06CM03666

Parcel: 11702274A


Addresses:

512 E 1ST ST


Inspection Status: Approved

Inspection History: ROOF NAILING

Permit Number - T06CM03666

Inspection Description - ROOF NAILING

Inspection Status - Approved

Date Description Inspector Results Comments
02/12/2007 ROOF NAILING Approved IVRS - Inspection :*
02/08/2007 ROOF NAILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 15 AMP WIRING MAY NOT BE USED IN 20 AMP CIRCUITS
2) 12-2/14-2 SAME BOX
3) NO WATER TEST DWV POTABLE OK
4) TERMINATE EXHAUST FAN TO EXTERIOR
5) GROUT TUB SHOES
6) BLOCK TUB WALLS
7) PROVIDE COPPER BOND
8) OVERSPAN SHOWER WALL
9) SECURE HOMERUNS
10) LAG BOLTS REQUIRED AT LEDGERS AT PORCH
11) MISSING ENCLOSED VENTING PER PLAN OVERHANG
12) GROUND METAL BOXES
13) MAKE UP ALL SWITCHES PIG TAIL GROUNDS
01/17/2007 ROOF NAILING Partial Approval IVRS - Inspection :*
01/08/2007 ROOF NAILING Not ready for Inspection IVRS - Inspection :*