Permit: T06CM03659

Parcel: 141314250

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T06CM03659

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
09/28/2006 FRAMING Approved IVRS - Inspection :*
09/26/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MISSING NUT ON H.D. BEHIND SHOWER
2) MISSING SHEAR REAR SOUTH
3) TIGHTEN ALL H.D. NUTS
4) BLK MECH AT GARAGE
09/22/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999$
1) SUPER PLEASE WALK JOB, MECH IS NOT COMPLETE, NOT DONE IN A WORKMANSHIP MANNER
2) MISSING AND EXHAUST FAN IN BATH NUMEROUS WIRES HAVE BEEN CUT, MISSING A H.D. BEHIND THE SHOWER SURROUND, CONDENSATE LINE IS IN THE WAY
NOTE: DRILLING HOLES IN SHEARWALL DEEP TO A MINIMUM