Inspection History Details
Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
Permit Number - T06CM03651
Inspection Description - EXCAVATION/LAYOUT REBAR & ZON
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/18/2006 | EXCAVATION/LAYOUT REBAR & ZON | Approved | IVRS - Inspection :* | |
08/16/2006 | EXCAVATION/LAYOUT REBAR & ZON | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) THE POST TENSION CABLE REPAIRS THAT WERE MADE DO NOT COMPLY WITH POST TENSION INSULATE STANDARD. EITHER REPAIR TO POST TENSION INSTALL STANDARDS OR HAVE ENGINEER OF RECORD PROVIDE CITY OF TUCSON APPROVED REPAIR. HAVE POST TENSION INSTITUITE REPAIR STANDARDS ON SITE FOR NEXT INSPECTION |
|
07/27/2006 | EXCAVATION/LAYOUT REBAR & ZON | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MANY CABLES HAVE SHEATHING DAMAGE MAKE APPROVED REPAIRS 2) LIVE ENDS HAVE TO MUCH CABLE EXPOSED ON CABLES 3) NEED NEW LSI AFTER 7/27/06 |