Permit: T06CM03639

Parcel: 11941015A


Addresses:

1919 W AJO WY

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
10/24/2006 FRAMING Approved IVRS - Inspection :*
10/20/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FILL DWV
2) FIRE STOP HOLES THROUGH TOP PLATES
3) NO SCREWS IN DRYER DUCT
10/06/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) STAPLE STUCCO MESH 6" ON CENTER AT TOP PLATES
2) TRIM MECH UNDER BAY OVERHANG
3) STAPLE MESH AT TOP OF COLUMNS
4) SEAL VAPOR BARRIER
5) FILL DWV
6) BLOCK MECH BOOTS
7) FIRE STOP AT KITCHEN/BATH
8) COMPLETE MECH CLOSET CEILING
9) COMPLETE EXHAUST DUCT IN BATH
10) STOPPED INSPECTION-HOUSE NOT READY