Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T06CM03635
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/20/2006 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
09/18/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
09/15/2006 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
09/13/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1. FINISH PREVIOUS ITEMS 2 & 4 2. ATTACH FIXTURE TO GRID 410.16 3. ELECTRIC SUPPORT TO BE AS PER 300.11 4. VDV CABLEING NEW & OLD TO BE SUPPORTED 725.3 & 6 AND 800.3 & 6 |
|
09/12/2006 | ELECTRIC - ABOVE CEILING | Denied | 1. 2X4 LIGHT FIXTURES IN GRID MUST HAVE 2 SEISMIC WIRES EACH, OPPOSITE CORNERS PER NEC. 2. MC CABLES MUST BE SUPPORTED PER CODE, WITHIN 12" EACH TERMINATION AND AT 6' INTERVALS, USE OWN SUPPORT WIRES. 3. J-BOXES MUST BE SUPPORTED TO STRUCTURE WIRES USED TO SUPPORT CONDUIT. BOXES MUST BE TIED OFF AT BOTH ENDS. 4. LIGHT FIXTURE MISSING IN BACK ROOM. |