Permit: T06CM03635

Parcel: 140160080

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T06CM03635

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
09/20/2006 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
09/18/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
09/15/2006 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
09/13/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1. FINISH PREVIOUS ITEMS 2 & 4
2. ATTACH FIXTURE TO GRID 410.16
3. ELECTRIC SUPPORT TO BE AS PER 300.11
4. VDV CABLEING NEW & OLD TO BE SUPPORTED 725.3 & 6 AND 800.3 & 6
09/12/2006 ELECTRIC - ABOVE CEILING Denied 1. 2X4 LIGHT FIXTURES IN GRID MUST HAVE 2 SEISMIC WIRES EACH, OPPOSITE CORNERS PER NEC.
2. MC CABLES MUST BE SUPPORTED PER CODE, WITHIN 12" EACH TERMINATION AND AT 6' INTERVALS, USE OWN SUPPORT WIRES.
3. J-BOXES MUST BE SUPPORTED TO STRUCTURE WIRES USED TO SUPPORT CONDUIT. BOXES MUST BE TIED OFF AT BOTH ENDS.
4. LIGHT FIXTURE MISSING IN BACK ROOM.