Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE RELOCATION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/23/2006 | ELECTRIC - SERVICE RELOCATION | Approved | IVRS - Inspection :* | |
| 06/21/2006 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SUPPORT HARDWARE FOR UNISTRAP INTO STRUCTURE HAS TO BE AT LEAST 1/4" (LAGS OK) 2. ROOF JACK TO BE SEALED 3. GROUND RODS TO BE GRADE OR BELOW 4. NEED BOTH GAS & WATER PIPING BOND 5. SUPPORT CONDUIT BETWEEN TWO LB'S AT SERVICE 6. LEAVE MESSAGE ON NEXT CALL IF OK TO ENTER. |