Permit: T06CM03624

Parcel: 129060850


Addresses:

2520 E 19TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE RELOCATION

Date Description Inspector Results Comments
06/23/2006 ELECTRIC - SERVICE RELOCATION Approved IVRS - Inspection :*
06/21/2006 ELECTRIC - SERVICE RELOCATION Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SUPPORT HARDWARE FOR UNISTRAP INTO STRUCTURE HAS TO BE AT LEAST 1/4" (LAGS OK)
2. ROOF JACK TO BE SEALED
3. GROUND RODS TO BE GRADE OR BELOW
4. NEED BOTH GAS & WATER PIPING BOND
5. SUPPORT CONDUIT BETWEEN TWO LB'S AT SERVICE
6. LEAVE MESSAGE ON NEXT CALL IF OK TO ENTER.