Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/05/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* OK FOR FINAL |
|
| 11/30/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* FINAL APPROVAL IS SUBJECT TO REGULAR MECHANICAL INSPECTOR. OK TEMP C OF O |
|
| 11/29/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MAKE UP AIR TO BE INTERLOCKED WITH HOOD EXHAUST IMC 508.1 2. EXISTING ROOFTOP UNIT IS NOT PROPERLY FUSED, BRANCH CKT RACEWAY BROKEN, CONDENSATE NOT PROPERLY SLOPED OR PROTECTED FROM SUN, SECURE TO ROOF. 3. MAKE SURE ALL EQUIPMENT IS PROPERLY IDENTIFIED IN PANEL SCHEDULE. OK TO INSTALL CEILING TILES. |
|
| 11/28/2006 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* CEILING COVERED PRIOR TO APPROVAL - RESCHEDULE WHEN CEILING IS OPEN FOR INSPECTION |