Permit: T06CM03595

Parcel: 13322500G


Addresses:

7159 E BROADWAY BL

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
12/05/2006 MECHANICAL - FINAL Approved IVRS - Inspection :*
OK FOR FINAL
11/30/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
FINAL APPROVAL IS SUBJECT TO REGULAR MECHANICAL INSPECTOR.
OK TEMP C OF O
11/29/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MAKE UP AIR TO BE INTERLOCKED WITH HOOD EXHAUST
IMC 508.1
2. EXISTING ROOFTOP UNIT IS NOT PROPERLY FUSED, BRANCH CKT RACEWAY BROKEN, CONDENSATE NOT PROPERLY SLOPED OR PROTECTED FROM SUN, SECURE TO ROOF.
3. MAKE SURE ALL EQUIPMENT IS PROPERLY IDENTIFIED IN PANEL SCHEDULE.

OK TO INSTALL CEILING TILES.
11/28/2006 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
CEILING COVERED PRIOR TO APPROVAL - RESCHEDULE WHEN CEILING IS OPEN FOR INSPECTION