Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/05/2006 | MECHANICAL - INTERMEDIATE | Approved | ||
| 08/31/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CHECKED FIRE WRAP. OK TO PROCEED. DO NOT PUT ANY CEILING TILES IN UNTIL ALL DUCT WORK IS REPAIRED AS NEEDED & STRAPPED. DUCTING HAS NEVER BEEN ALLOWED TO LAY ON CEILING TILES & GRID. YOU MIGHT NOT BE ABLE TO PASS Y0UR AIR BALANCE TEST IF DUCTS ARE BROKEN, KINKED, OR SAGGING. RECALL FOR INSPECTION PRIOR TO CEILING TILES. |
|
| 08/30/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CHECKED WELDS ON GREASE DUCT. OK TO FIRE WRAP & INSTALL. EXISTING DUCT WORK COMING APART. MUST BE STRAPPED UP OFF OF GRID. ON FINAL PROVIDE AN AUDIBLE & VISIBLE ALARM FOR DUCT SMOKE DETECTOR & COPIES OF CERTIFIED AIR BALANCE REPORTS FOR EXHAUST HOOD & HVAC SYSTEM. |