Permit: T06CM03595

Parcel: 13322500G


Addresses:

7159 E BROADWAY BL

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
12/05/2006 MECHANICAL - INTERMEDIATE Approved
08/31/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
CHECKED FIRE WRAP. OK TO PROCEED.
DO NOT PUT ANY CEILING TILES IN UNTIL ALL DUCT WORK IS REPAIRED AS NEEDED & STRAPPED. DUCTING HAS NEVER BEEN ALLOWED TO LAY ON CEILING TILES & GRID. YOU MIGHT NOT BE ABLE TO PASS Y0UR AIR BALANCE TEST IF DUCTS ARE BROKEN, KINKED, OR SAGGING. RECALL FOR INSPECTION PRIOR TO CEILING TILES.
08/30/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
CHECKED WELDS ON GREASE DUCT.
OK TO FIRE WRAP & INSTALL.
EXISTING DUCT WORK COMING APART.
MUST BE STRAPPED UP OFF OF GRID.
ON FINAL PROVIDE AN AUDIBLE & VISIBLE ALARM FOR DUCT SMOKE DETECTOR & COPIES OF CERTIFIED AIR BALANCE REPORTS FOR EXHAUST HOOD & HVAC SYSTEM.