Permit: T06CM03595

Parcel: 13322500G


Addresses:

7159 E BROADWAY BL

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
11/28/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
11/22/2006 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1) GAS PIPING TO RTU OK
2) PRESSURE TEST OK
3) RECEIVED BACK FLOW CERTS ?
4) W C REQUIRED TO BE SEALED AT CONTACT TO FLOOR
5) SUPPORT SODA DRAIN PIPING WITH PIPE CLAMPS
6) INSTALL ICE MAKER OR REVISE IF DESIRED
7) PROTECT ABS VENT PENETRATION
8) RESTROOMS AND W H SAFETY DEVICES ARE COMPLETE
11/02/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
GAS PIPING TO NEW RTU TO BE PER PLAN
1. GAS PIPING TEST SHALL BE HOLDING MINIMUM TEST PRESSURE.
2. SEAL PENETRATION OUT OF BUILDING FOR T&P DRAIN.
3. ALL FIXTURES & APPLIANCES TO BE INSTALLED & HOOK UPS COMPLETED CORRECTLY TO ALL EQUIPMENT.
4. ALL FIXTURES TO BE MADE WATER TIGHT.
5. NO COPPER SHALL BE DOWN STREAM OF CARBONATOR BACKFLOW SUPPLY.
6. ALL CLEANOUTS SHALL HAVE FACTORY TAPPED PLUG WITH MACHINE SCREWS.
7. ALL BACKFLOW CERTIFICATIONS TO BE ON SITE.

NOT COMPLETE LIST
PROVIDE LISTING FOR WATER HEATER STAND.