Permit: T06CM03595

Parcel: 13322500G


Addresses:

7159 E BROADWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/01/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/30/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. FINISH PREVIOUS ITEMS
2. RECEPTACLE COVERS TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO 406.8
11/29/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. SECURE M/C CABLE TO RACEWAY - INTERIOR SIGN.
2. FILL UNUSED OPENINGS IN RACEWAY.
3. INSTALL MARKING LABEL 600.4
4. PLEASE PROVIDE LADDER FOR ROOF ACCESS.
5. FINISH PREVIOUS ITEMS #1
11/28/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. EM LIGHTING & EXIT LIGHTING TO BE ON CIRCUIT FOR AREA SERVED 700.12
2. CLEAN EXCESS DUST AND DIRT OUT OF PANELS.
3. USE APPROPRIATE SIZE SCREWS FOR PANEL COVERS.
4. BOXES MORE THAN 1/4" FROM BOX TO SURFACE IN NON-COMBUSTIBLES TO USE AN APPROVED EXTENDER
RING 314.20
5. FILL UNUSED OPENING IN LIGHT FIXTURE.
6. PROPERLY INSTALL CORD CAP TO CORD
7. FIXTURES TO BE ATTACHED TO GRID 410.16
8. PLEASE VERIFY LISTING OF KITCHEN EQUIPMENT - STEAM TABLE.

ROOF
9. PROTECT CAR FLEX FROM SHARP METAL EDGES.
10. TIGHTEN LOOSE FITTINGS.
11. M/C ARMOR IS BROKEN.
12. WHRE IS MAINTENANCE RECPT 210.63
13. LABEL PANEL COVERS
11/01/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. VERIFY DERATING OF CONDUCTOR PER 310.15
2. VDV CABELING TO BE PER 725.3 & 6, 800.3 & 6
3. ONLY ONE NEUTRAL CONDUCTOR PER TERMINAL LUG.
4. PLEASE ADD 02036 - ABOVE CEILING TO PERMIT

OK TEMP POWER TO TEST
SUBJECT TO POSTING OF BOND.