Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/01/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/30/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. FINISH PREVIOUS ITEMS 2. RECEPTACLE COVERS TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO 406.8 |
|
| 11/29/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. SECURE M/C CABLE TO RACEWAY - INTERIOR SIGN. 2. FILL UNUSED OPENINGS IN RACEWAY. 3. INSTALL MARKING LABEL 600.4 4. PLEASE PROVIDE LADDER FOR ROOF ACCESS. 5. FINISH PREVIOUS ITEMS #1 |
|
| 11/28/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. EM LIGHTING & EXIT LIGHTING TO BE ON CIRCUIT FOR AREA SERVED 700.12 2. CLEAN EXCESS DUST AND DIRT OUT OF PANELS. 3. USE APPROPRIATE SIZE SCREWS FOR PANEL COVERS. 4. BOXES MORE THAN 1/4" FROM BOX TO SURFACE IN NON-COMBUSTIBLES TO USE AN APPROVED EXTENDER RING 314.20 5. FILL UNUSED OPENING IN LIGHT FIXTURE. 6. PROPERLY INSTALL CORD CAP TO CORD 7. FIXTURES TO BE ATTACHED TO GRID 410.16 8. PLEASE VERIFY LISTING OF KITCHEN EQUIPMENT - STEAM TABLE. ROOF 9. PROTECT CAR FLEX FROM SHARP METAL EDGES. 10. TIGHTEN LOOSE FITTINGS. 11. M/C ARMOR IS BROKEN. 12. WHRE IS MAINTENANCE RECPT 210.63 13. LABEL PANEL COVERS |
|
| 11/01/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. VERIFY DERATING OF CONDUCTOR PER 310.15 2. VDV CABELING TO BE PER 725.3 & 6, 800.3 & 6 3. ONLY ONE NEUTRAL CONDUCTOR PER TERMINAL LUG. 4. PLEASE ADD 02036 - ABOVE CEILING TO PERMIT OK TEMP POWER TO TEST SUBJECT TO POSTING OF BOND. |