Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/08/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* OK WALLS RECEIVED M/C LETTER |
|
| 08/31/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. DO NOT BUNDLE M/C CABLES 2. SUPPORT M/C CABLE 12" OF PANEL 3. MAINTAIN DEDICATED SPACE BELOW PANEL 4. VDV CABLEING TO BE PROTECTED AT STUDS ALSO SPLICES TO BE ACCESSIBLE. 5. PLEASE PROVIDE A LETTER AUTHORIZING USAGE OF M/C CABLE. 6. FILL UNUSED OPENINGS IN PANEL OK WALLS EXCEPT PANELS SUBJECT TO M/C LETTER |