Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T06CM03586
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/11/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 1. CORRECTIONS MADE OK 2. PLUMBING FINAL OK 3. OK FOR C OF O |
|
05/09/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
05/07/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. SUPPLY LISTING PLATE FOR COFFEE ROASTER NSF AGA CSA UPC ETC 2. SUPPLY LISTING RATING FOR FLEX CONNECTOR AT ROASTER 3. EACH WATER SUPPLIED DEVICE TO HAVE APPROVED BACKFLOW PROTECTION 4. ALL INDIRECT WASTE PIPING TO BE APPROVED MATERIAL 5. ALL I.W PIPING TO HAVE AIR GAP |
|
03/09/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. TRAP AND TRAP ARM TO BE THE SAME SIZE 2. HARD PIPE T&P RELIEF DRAIN 3. SUPPORT EXPANSION TANK 4. SUPPORT GAS PIPE AT ROASTER - COMPLETE VENT 5. SEE NOTE #16 OF PLUMBING NOTES |