Permit: T06CM03586

Parcel: 124041020

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/10/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/07/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. AIM EMERGENCY LIGHTS DOWN & OUT SO THEY ARE EFFECTIVE.
2. EMERGENCY LIGHTING TO BE POWERED BY LIGHTING CKT THAT FEEDS THE NORMAL LIGHTING CKT FOR THAT AREA (NOT HOME RUN) - NEC 700.12
3. STRAP WATER HEATER FLEX AND PROVIDE MINIMUM #10 CU GROUND
4. CEILING AREA LIGHTING ABOVE SALES
A. GROUND BOXES -- NEC 250
B. SECURE MC WITHIN 12" OF TERMINATIONS - NEC 330.30
C. CHECK BOX FILL -- NEC 314.16
D. PROVIDE INSTALLATION INSTRUCTIONS FOR LOW
VOLTAGE LIGHTING LOW VOLTAGE WIRING TO BE PROTECTED GOING INTO BOXES, TRANSFORMERS NOT TO BE OVERLOADED, ETC. --- PROVIDE INSTRUCTIONS NEC 110.3B

PARTIAL INSPECTION ONLY
04/02/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
03/30/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
HAVE ELECTRICIAN ON SITE AND HAVE ALL EQUIPMENT OPEN FOR INSPECTION.
03/08/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*