Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM03586
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/10/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
05/07/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. AIM EMERGENCY LIGHTS DOWN & OUT SO THEY ARE EFFECTIVE. 2. EMERGENCY LIGHTING TO BE POWERED BY LIGHTING CKT THAT FEEDS THE NORMAL LIGHTING CKT FOR THAT AREA (NOT HOME RUN) - NEC 700.12 3. STRAP WATER HEATER FLEX AND PROVIDE MINIMUM #10 CU GROUND 4. CEILING AREA LIGHTING ABOVE SALES A. GROUND BOXES -- NEC 250 B. SECURE MC WITHIN 12" OF TERMINATIONS - NEC 330.30 C. CHECK BOX FILL -- NEC 314.16 D. PROVIDE INSTALLATION INSTRUCTIONS FOR LOW VOLTAGE LIGHTING LOW VOLTAGE WIRING TO BE PROTECTED GOING INTO BOXES, TRANSFORMERS NOT TO BE OVERLOADED, ETC. --- PROVIDE INSTRUCTIONS NEC 110.3B PARTIAL INSPECTION ONLY |
|
04/02/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
03/30/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* HAVE ELECTRICIAN ON SITE AND HAVE ALL EQUIPMENT OPEN FOR INSPECTION. |
|
03/08/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |