Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/25/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 08/25/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* ILLUMINATION AT PANEL REVISE CIRCUIT DIRECTORY BOX SUPPORTS FOR FIXTURE OVER 6LBS. |
|
| 08/24/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. INSTALL BOX AT LIGHT FIXTURE FOR RATING OVER 6 LBS. 2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 314.20 3. SUPPORT WIRE NEEDED FOR CANS AND LIGHT FIXTURES. 4. FILL UNUSED OPENINGS IN BOXES 5. SUPPORT BOXES 6. SUPPORT M/C CABLE WITHIN 12" OF BOXES 7. OLD VDV CABLEING TO BE AS PER 725.3&6, 800.3&6 8. NEW ELECTRIC FOR LIGHTING HAS BEEN ADDED SINCE INTERMEDIATE PLEASE REVISE PLANS. 9. PLEASE VERIFY HOME RUNS FOR PATIENT CARE AREAS ARE AS PER 517.13 10. UNIT IS BEING OCCUPIED CANNOT ACCESS ALL AREAS 11. FINISH ELECTRIC |
|
| 08/23/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELLED BY CHRIS |