Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/16/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/19/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SEE NOTES LAST INSP. 1. PRIOR TO INTER. INSPECTION APPROVAL A LETTER AS REQUIRED PER NOTES FOR USE OF MC 2. INSTALL GROUND TAILS IN METAL BOXES BEFORE TRIM OUT FOR INSP. APPROVAL. 3. OK ROUGH PER CODE, WALLS ONLY. |
|
| 09/15/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PROVIDE LETTER FOR MC USE PER NOTE LAST INSP. 2. COMPLETE LIGHT SWITCH INSTALL BY DOORS. |
|
| 08/28/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EMT TO BE SUPPORTED WITHIN 3' OF TERMINATION, MC TO WITHIN 12" (PER NEC) 2. PER NOTE #3 PLANS CALL FOR EMT OR IMC CONDUIT. PROVIDE LETTER FROM ARCH. FOR APPROVAL OF MC CABLE USE. 3. WALLS NOT COMPLETE |