Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T06CM03564
Inspection Description - FRAMING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/25/2006 | FRAMING | Approved | IVRS - Inspection :* | |
| 09/18/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WEST SIDE GARAGE DOOR OPENING-NO TRIMMERS 2) WINDOW MISSING WEST SIDE 3) 2 X 8 LEDGER GARAGE NEED BLOCKING AT LEDGER SPLICE 4) VENT DUCTS LIVING ROOM 5) PEX LINES IN KITCHEN CEILING NEED TO HAVE 12" MINIMUM FROM CAN LIGHTS 6) ELECTRICAL BOX KITCHEN COUNTER 7) ALL DUCT VENTS NEED TO BE BLOCKED 8) ANCHOR BOLT KITCHEN SHEARWALL NOT TIGHTENED 9) STOPPED INSPECTION |