Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/21/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE. |
|
| 06/16/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* DO NOT USE A FLEX APPLIANCE CONNECTOR IN THE ATTIC TO COUPLE GAS PIPE. RETEST SYSTEM AFTER REPAIR. TERMINATE CONDENSATE TO WITHIN 6" OF THE GROUND. PAINT EXPOSED PVC W/LATEX PAINT ADD ANOTHER BLOCK & CLAMP. SECURE GAS PIPE ON ROOF 3/8" ID X 36" GAS FLEX NOT ADEQUATE FOR 120,000 BTU. #8 ROMEX ONLY GOOD FOR 40 AMPS. CHANGE TO #6 OR USE 90 DEG. WIRE #8 |