Permit: T06CM03554

Parcel: 120062140


Addresses:

134 E PALMDALE ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/03/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/26/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio
THIS IS THE 3RD. INSP DENIED FOR THE SAME THING.
A RE-INSPECTION FEE IS ASSESSED,
PAY REFEE AT 201 N. STONE

- BOND THE BUSHING AT THE OFFSET NIPPLE
10/06/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
SEE NOTES LAST INSP.
09/27/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
BOND THE BUSHINGS AT 1 1/4" TERMINATION INTO PANEL.
08/24/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*