Permit: T06CM03553

Parcel: 136326450


Addresses:

10825 E SKY HIGH DR

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
01/11/2008 BUILDING - FINAL Approved IVRS - Inspection :*
01/07/2008 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL VACUUM BREAKER FRONT HOSE BIB
2) MAX BREAKER EAST A/C 35 AMPS
3) GROUND WIRE NOT CONNECTED AT MAIN PANEL
4) ALL LIGHTS AND SMOKIES IN BEDROOM TO BE ARC FAULT
5) GARAGE CIRCUIT HAS HOT/NEUTRAL, REVERSED
6) RECEPT BY REFER NOT GFI
7) SECURE A/C WHIPS WITHIN 12" OF DISCONNECT
8) INSTALL SECONDARY DRAINS OR CUT OFF SWITCHES ON FURNACES
9) INSTALL LENS S.E. BEDROOM CLOSET
10) FLOURESCENT FIXTURE WEST BEDROOM CLOSET TO CLEAR VERTICAL LINE FROM SHELF FRONT MINIMUM 6"
11) RECEPT WEST BATH INOPERABLE
12) UNABLE TO LOCATE RESET FOR EXTERIOR RECEPTS
13) EXTERIOR RECEPT NEAR BBQ INOPERABLE
14) COMPLETE VENTING OF SLEEVE FOR BBQ GAS LINE