Permit: T06CM03541

Parcel: 141153550

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
10/26/2006 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
09/27/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
CONDENSATE IN WALL OK TO COVER
09/26/2006 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
09/25/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1 1/2" DUCT INSULATION DOES NOT MEET MIN. R-5 REQUIREMENT.
PLANS REQUIRE 1 1/2" DUCT LINES.
SUPPLY & EXHAUST IN RESTROOMS OK TO SHEETROCK
PROVIDE CONDENSATE DRAIN LINE IN WALL AS PER PLANS.