Date Description Inspector Results Comments
09/15/2006 ELECTRIC - FINAL Approved
09/12/2006 ELECTRIC - FINAL Partial Approval JERRY MARTIN 591-2019

CHECK FOR $108.00 RECEIVED
AC NORTH UNIT
1. STRAP FLEX
2. FIX DISCONNECT COVER SO IT CLOSES

AC SOUTH UNIT
1. MAX 50 AMP FUSE

INSIDE
1. PROVIDE DISCONNECTION MEANS PER NEC 2002 422.31(B) FOR BATHROOM INSTA HOT.
2. PANEL DIRECTORY NOT CORRECTLY IDENTIFIED - NEC 408.4
3. HAVE LOOSE DEVICES AND BOXES IN WALLS --
NEC 406.4 & 314.23

OK TO OCCUPY
09/08/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. POWER NEEDS TO BE ON BEFORE FINAL INSPECTION.
2. CEILING TILES HAVE NOT BEEN APPROVED TO BE INSTALLED AND MUST BE REMOVED PRIOR TO FINAL INSPECTION.
3. ENTRY LIGHTING THAT IS COVERED IN WALL MUST EITHER BE REMOVED OR EXPOSE J-BOXES FOR LIGHTS AND INSTALL LIGHTS OR BLANK COVERS.
09/07/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
SERVICE INSPECTION ONLY
#4 BOND SERVICE RACEWAY INTO METER AND METER TO DISCONNECT IDENTIFY SERVICE DISCONNECTS.
DO NOT CALL FOR FINAL UNTIL ENERGIZED