Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM03534
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/29/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. DISCONNECT FOR UNIT IS LOOSE AND IN A STATE OF DISREPAIR. 2. NEED PROPER SIZE AND TYPE CORD TO SUB-PANEL 3. SEPARATE NEUTRALS AND GROUNDS IN SUB-PANEL AND USE CONNECTOR FOR SUPPLY CORD. 4. INSTALL WORKING SMOKE DETECTORS IN BEDROOMS AND HALLWAY. 5. SAFE OFF ALL OPEN WIRING AND REPAIR OR REPLACE ALL DAMAGED DEVICES AND LIGHT FIXTURES. |