Permit: T06CM03525

Parcel: 140550790

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
09/28/2006 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
1) NEED TO REPLACE PLYWOOD NAILED TO SHEAR TRANSFER
09/22/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE EQUIVILENT RETRO FOR CBSQ46 MISSING AT GARAGE X 4
2) GARAGE SHEAR REQUIRES 4" ON CENTER NAILING
3) REMOVE DOOR BUCKS TO ALLOW DBL SHEAR AT GARAGE
4) 4 X 6 POSTS REQUIRED AT GARAGE
5) TRIPLE KINGS AND STRAPS REQUIRED AT GARAGE HDR
6) STRAP STAIRWAY HDR TO POSTS-BOTH SIDES
7) RAT RUN IN L.R. TRUSSES PER SPEC.
8) EPOXY ALL HOLDOWNS
9) SHEAR END OF TRUSSES OVER ENTRY PER 7/DT1
10) STOPPED INSPECTION