Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T06CM03521
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/20/2007 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
02/09/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GFCI BATH INOPERATIVE 2) INSTALL DRAIN PAN UNDER H20 HEATER, SIZED AND DRAINED ACCORDINGLY 3) CUT SEWER CLEANOUTS TO GRADE 4) ELECTRIC H20 HEATER HAS SEPERATE FUSED DISONNECT-CANNOT LOCATE |
|
02/05/2007 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED PER CONTRACTOR |
|