Permit: T06CM03518

Parcel: 128112630


Addresses:

4858 E CECELIA ST


Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T06CM03518

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/22/2006 BUILDING - FINAL Approved IVRS - Inspection :*
07/28/2006 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEAL OPEN KNOCKOUTS IN PANEL DEADFRONT
2) EAST LAUNDRY OUTLET HAS NO POWER
3) EXTERIOR CONDUIT OUTLETS NEED GFI PROTECTION
4) NEED HOODED LIGHT
5) FINISH WATER HEATER INSTALLATION
07/24/2006 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED ALL ELECTRIC ON FOR INSPECTION AND ACCESS TO PANELS
2) NEED TO SHEETROCK LAUNDRY ROOM
3) DRYER VENT DUCT IS OVER SPANNED MAX 25' -5' FOR EACH 90 DEGREE ELBOW, -2 1/2' FOR EACH 45 DEGREE
4) NEED SMOKIES IN HALL AND ALL BEDROOMS
5) NEED 3/4" DRAIN ON TPR VALVE AND DRAIN NEEDS TO RUN IN DOWN DIRECTION TO EXTERIOR OF HOUSE
6) NEED COMBUSTION AND RELIEF AIR FOR HOT WATER HEATER