Permit: T06CM03508

Parcel: 13634608B


Addresses:

3655 S KOLB RD

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/18/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
12/14/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. SHALL PROVIDE DIELECTRIC PROTECTIONFOR DISSIMILAR MATERIALS. AT WATER TAKE OFFS AT WATER HEATER AREA
2. SHALL SUPPORT WATER HEATER EXPANSION TANK.
3. WATER HEATER TEMPERATURE & PRESSURE RELIEF TO HAVE FULL SIZE APPROVED MATERIAL FOR DRAIN TO DAYLIGHT.
12/07/2006 PLUMBING - FINAL Not ready for Inspection SHALL SEE SINK INSTALL WITH AIR ADMITTANCE VALVE IN REAR OFFICE. BACKFLOW CERTIFICATIONS TURNED IN.
11/07/2006 PLUMBING - FINAL Partial Approval 1. SHALL PROVIDE SEPARATE DRAINS FOR 009'S OR UP SIZE TO ACCOMODATE FULL FLOW FROM ALL DEVICES MANIFOLDED TOGETHER.
2. SHALL BE NOT COPPER OR BRASS PIPING DOWNSTREAM
OF 009'S SERVING CARBONATORS. ADDRESS THIS IMMEDIATELY!