Inspection History Details
Permit: T06CM03501
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/30/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. CALL FOR ELECTRICAL FINAL AFTER UNITS ARE OPERATIONAL. 2. "OFF" AND "ON" NOT MARKED PROPERLY ON DISCONNECT FACE PLATE. |
|
| 06/29/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED DEDICATED BRANCH CKT TO UNIT HEATER/S 2. PROPERLY IDENTIFY UNITS IN PANEL DIRECTORY. 3. EXISTING J-BOXES USE ARE OVERFILLED AND NEED TO BE PROPERLY GROUNDED WITH THE EQUIPMENT GROUND CONDUCTOR. 4. PROVIDE INSTALLATION MANUAL FOR UNITS. |
|
| 06/27/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |