Inspection History Details
Permit: T06CM03501
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/30/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 06/29/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 06/27/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) CORRECTLY IDENTIFY UNIT HEATERS AND ANY RELOCATED CKT'S ON PANEL DIRECTORY 2) PROVIDE A DISCONNECT FOR EACH HEATER 3) PROVIDE EQUIPMENT GROUND FOR EACH HEATER 4) CHECK J-BOX FILL AND PROVIDE LADDER SO I CAN CHECK CEILING J-BOX FILL |