Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/16/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/15/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUNDING CONDUCTORS #6 & SMALLER TO BE IDENTIFIED ALONG ENTIRE LENGTH CANNOT USE BLUE OR WHITE WIRES 2. CONDUCTORS #4 & LARGER NEED PROTECTIVE BUSHING 3. SEAL OPEN KNOCKOUTS IN CARWASH CABINET 4. PANEL DIRECTORY NOT PER PLAN 5. HAVE ELECTRICAL CONTRACTOR ON SITE FOR INSPECTION 6. RECALL WHEN READY |