Permit: T06CM03499

Parcel: 14117005C


Addresses:

7335 S HOUGHTON RD


Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Permit Number - T06CM03499

Inspection Description - ELECTRIC - UFER

Inspection Status - Approved

Date Description Inspector Results Comments
01/16/2008 ELECTRIC - UFER Approved
09/12/2007 ELECTRIC - UFER Partial Approval IVRS - Inspection :*
1. OK 3/0 COPPER TO REBAR IN FOOTING
2. NEC 225.30 ALLOWS ONLY ONE FEEDER TO ADDITIONAL BUILDING SERVED ON LOAD SIDE OF SERVICE DISCONNECT
3. 225.31 & 225.32 REQUIRES DISCONNECT FOR FEEDER TO OTHER BUILDING & REQUIRES THIS DISCONNECT TO BE LOCATED INSIDE OR OUTSIDE OF BUILDING SERVED