Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
Permit Number - T06CM03499
Inspection Description - ELECTRIC - UFER
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/16/2008 | ELECTRIC - UFER | Approved | ||
09/12/2007 | ELECTRIC - UFER | Partial Approval | IVRS - Inspection :* 1. OK 3/0 COPPER TO REBAR IN FOOTING 2. NEC 225.30 ALLOWS ONLY ONE FEEDER TO ADDITIONAL BUILDING SERVED ON LOAD SIDE OF SERVICE DISCONNECT 3. 225.31 & 225.32 REQUIRES DISCONNECT FOR FEEDER TO OTHER BUILDING & REQUIRES THIS DISCONNECT TO BE LOCATED INSIDE OR OUTSIDE OF BUILDING SERVED |